Duct Size Calculator

Size round and rectangular ducts from airflow and velocity.

CFM
FPM
in
Round duct diameter10.24in
Next standard size11in
Duct area82.286in²
Rectangular width at 8 in high10.29in
A = Q / V = 400 CFM / 700 FPM = 0.57143 ft² d = √(4A/π) × 12 = 10.24 in
Velocity method. Typical residential velocities: 600–900 FPM for supply trunks, 400–600 FPM for branches. Equal-friction design and fitting losses need a full Manual D calculation.

Runs entirely in your browser — nothing you enter is uploaded.

About this tool

Choose duct sizes for HVAC supply and return runs using the velocity method.

How to use the Duct Size Calculator

  1. Enter the airflow, design velocity and rectangular duct height (optional).
  2. The result updates instantly, with the working shown underneath.
  3. Use Copy to grab a result, or Reset to start again.

How it works

Required area = airflow ÷ velocity; the round diameter follows from the circle area.

Formula

A = Q / V; d = √(4A/π)

Frequently asked questions

What velocity should I use?

Residential trunks commonly use 700–900 FPM and branches 500–600 FPM to limit noise.